Answer: The fundamental cause of vibration and whistling is improper selection, especially an excessively high CV value and insufficient throttling level.
I. Why do vibrations and whistling occur?
The CV value is set too high: When the valve operates at a small opening (<30%) for a long time, the medium flow rate is too high, causing high-frequency vibration and sharp whistling
Insufficient throttling level: The pressure difference of the reheater's desuperheating water is large, and the single-layer sleeve cannot effectively reduce the pressure, resulting in flash evaporation and cavitation
Insufficient closing force: The thrust of the actuator is too small, the valve cannot be closed tightly, and the medium continuously eroses the sealing surface
Ii. What should be noted when selecting a model?
1. Verify the actual parameters on site: Do not merely look at the design drawings; it is necessary to verify the real data such as the pressure, pressure difference, temperature, and flow rate before and after the valve
2. Accurately calculate the CV value: Ensure that the valve operates within the 30% to 80% opening range and avoid long-term operation at a small opening
3. Select an appropriate throttling structure: For high-pressure differential conditions, multi-layer sleeves or multi-stage pressure reduction structures must be chosen
4. Confirm the closing force and sealing material: The thrust of the actuator should be sufficient, and the sealing surface should be surfacing with hard alloy.
Viti Tip: Over 80% of the problems with the desuperheating water regulating valve occur during the selection process. Viti adheres to the service process of "diagnosing on-site parameters first and then precisely calculating and selecting the model", avoiding problems such as vibration, whistling and internal leakage from the source.